5.3. ADVANCED SETTINGS
* OR: activates the OR button for the I/O configuration column (see previous point). The window that
appears when the OR button is pressed can be seen in figure 4.12
* NOT: when NOT checkbox is enabled, the logic is inverted. The element (input, output, LED) will actuate
when the conditions are NOT fulfilled.
* NAME: the user can write an identifying label of up to 4 characters that will get stored to be displayed later
on.
* BLINK (only for LEDs): the selection of BLINK checkbox makes the LED blink (alternatively switch ON and
OFF) instead of being fixed when it is activated.
* MEMORY (only for outputs and LEDs): when MEMORY checkbox is enabled, the respective element will be
latched. If the cause that generated the activation of the output or LED does no longer exist, the element will
remain active until a RESET command is performed.
4-10
FIGURE 4-12. OR ASSIGNMENT
MIF Digital Feeder Protection