13.5
ERRORS
When any of the previous commands cause an error in the slave, we will receive the following string:
ADDRESS
FUNCTIÓN+
80H
01
90
The ERROR CODE field may contain the following values:
01
ILLEGAL FUNCTION
02
ILLEGAL DATA ADDRESS
03
ILLEGAL DATA VALUE
04
SLAVE DEVICE FAILURE
05
ACK.
06
SLAVE BUSY
07
NEGATIVE ACKNOWLEDGE
08
MEMORY PARITY ERROR
GEK-106273L
ANNEX 3 MODBUS MEMORY MAP
ERROR
CRC
CODE
07
0D C2