GE GEK-106273L Instruction Manual page 122

Digital feeder protection
Table of Contents

Advertisement

Mnemonics appearing in the ADVANCED SETTINGS group, only for OPTION 2 models:
I^2
I^2 MAX
CLP
CLP ENABLE
T IN
T OUT
K 5OP
K 51P
BF
BF ENABLE
BF TIME
GEK-106273L
KEYPAD AND DISPLAY
2
I
counter
2
Alarm level for I
0 – 999.0 kA2
Cold load pickup
Permission CLP
Y (YES) / N (NO)
Pickup timer setting
1 – 60 seg.
Drop out timer setting
1 – 60 seg.
Multiplier for 50P tap
1 – 5
Multiplier for 51P tap
1 – 5
Breaker failure to open
Permission BF
Y (YES) / N (NO)
Breaker failure to open time
50 – 999 msec.
MIF Digital Feeder Protection
Step: 0.001
Step: 0.001
Step: 0.001
Step: 0.01
Step: 0.01
Step: 1 msec.