GE GEK-106273L Instruction Manual page 187

Digital feeder protection
Table of Contents

Advertisement

ENUM_BAUDIOS
VALUE
MEANING
0x01
300
0x02
600
0x04
1200
0x08
2400
0x10
4800
0x20
9600
0x40
19200
ENUM_CURVA
VALUE
MEANING
0x01
INVERSE
0x02
VERY INVERSE
0x04
EXTREMELY INVERSE
0x08
DEFINITE TIME
DATE
Milliseconds passed from the 1st of January, 1996 at 00:00:00.000.
The size of DATE type is 6 bytes ordered in INTEL format.
EXAMPLE:
31st of May, 1999, at 10:01:04.224 = 107,690,464,000 milliseconds from 1/1/1996, 00:00:00.000
107,690,464,000 DEC = 00 19 12 DA 13 00 HEX = 00 13 DA 12 19 00 (lower bytes first)
OPERATIONS
NAME
ENGLISH
RL
RESET LEDS
RIt
RESET THERMAL IMAGE
acT1
ACTIVATE TABLE 1
acT2
ACTIVATE TABLE 2
Settings
SELECTION / CONFIRMAT.
13-12
ANNEX 3 MODBUS MEMORY MAP
SELECTION
CONFIRMATION
09
03
0D
0F
01
MIF Digital Feeder Protection
13.6.3.
0A
04
0E
10
02
SPECIAL FORMATS
GEK-106273L

Advertisement

Table of Contents
loading

Table of Contents