GE GEK-106273L Instruction Manual page 142

Digital feeder protection
Table of Contents

Advertisement

RELAY COMMISSIONING
General Settings (Adv.)
Identification
Active Table
Trip Contact - Minimum
time closed.
Phase TOC (Table 2)
51P Permission to Trip
51P Tap / Pickup Value
51P Curve Type
51P Time Dial
51P Definite Time Delay
Ground TOC (Table 2)
51N Permission to Trip
51N Tap / Pickup (1/5 A
ground)
51N
Tap
/
Pickup
(sensitive ground)
51N Curve Type
51N Time Dial
51N Definite Time Delay
Ph IOC High Set Table 2
50PH Permission to Trip
50PH Tap / Pickup
50PH Time Delay
Ph IOC Low Set Table 2
50PL Permission to Trip
50PL Tap / Pickup
50PL Time Delay
Gnd IOC High Set Table
2
50NH Permission to Trip
50NH Tap / Pickup (1/5 A
ground)
50NH
Tap
/
Pickup
(sensitive ground)
50NH Time Delay
GEK-106273L
ENERVISTA MII
SETUP
GENERAL SET. ADV.
IDENTIFICATION
ACTIVE TABLE
TRIP MINIMUM TIME
51P Function (Table
2)
51P Trip Permission
51P Pickup T2
51P Curve Type T2
51P Time Dial T2
51P Definite Time T2
51N Function (Table
2)
51N Trip Permission
51N Pickup T2
51N Pickup T2
51N Curve Type T2
51N Time Dial T2
51N Definite Time T2
50PH Function (Table
2)
50PH Trip Permission
50PH Pickup T2
50PH Time Delay T2
50PL Function (Table
2)
50PL Trip Permission
50PL Pickup T2
50PL Time Delay T2
50NH Funct. (Table 2)
50NH Trip Permission
50NH Pickup T2
50NH Pickup T2
50NH Time Delay T2
MIF Digital Feeder Protection
9.21.2.
USER
HMI
VALUE
GENERAL
ADVANCED
---
TAB
TRIP MIN
TIME
F51P T2
TRIP 51P T2
TAP 51P T2
CURV 51P T2
DIAL 51P T2
TIME 51P T2
F51N T2
TRIP 51N T2
TAP 51N T2
TAP 51N T2
CURV 51N T2
DIAL 51N T2
TIME 51N T2
F50PH T2
TRIP 50PH T2
TAP 50PH T2
TIME 50PH T2
F50PL T2
TRIP 50PL T2
TAP 50PL T2
TIME 50PL T2
F50NH T2
TRIP 50NH T2
TAP 50NH T2
TAP 50NH T2
TIME 50NH T2
ADVANCED SETTINGS
RANGE
STEP
Text
NA
1 – 2
NA
50 – 300 ms.
1 ms.
Y/N
NA
0.1 – 2.4 In (Ph)
0.01 In (P)
INV, V.I.,E.I.,
NA
0.05 – 2.00 (IEC)
0.01
0.5 – 20.0 (ANSI)
0.01
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 2.4 In
0.01 In (G)
(Gnd)
0.005-0.12 A
0.001 A
INV, M.I.,E.I.,
NA
0.05 – 2.00 (IEC)
0.01
0.5 – 20.0 (ANSI)
0.01
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In (Ph) 0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In (Ph) 0.1 In (Ph)
0 – 600.00 s.
0.01 s.
Y/N
NA
0.1 – 30 In (Gnd)
0.1 In (G)
0.005-0.12 A
0.001 A
0 – 600.00 s.
0.01 s.
9-15