Analog Value Representation - Siemens SINUMERIK 828D PPU Series Manual

Hide thumbs Also See for SINUMERIK 828D PPU Series:
Table of Contents

Advertisement

Examples of programming
52. Determine control type:
53. Set the operating mode:
54. Query the error status bit in cyclic operation:
7.5.4.3

Analog value representation

NOTICE
The analog values of the inputs and outputs are written or read in 16 bit data format i.e.
they must be accessed word by word.
The analog values are provided as 16 bit integer values. Depending on the operating mode,
the measured values must be converted using the following factors in order to achieve the
corresponding physical value.
Factor (AI):
Factor (AO):
Calculation: 16 bit value (hex. or dec.) * factor = measured value
PPU
Manual, 11/2010, 6FC5397-2DP10-1BA0
Voltage [V]
0.00151947
0.000381469
Current [mA]
0.003051758
0.0007629
Connectable components
7.5 PP 72/48D 2/2A PN
Temperature [°C]
0.1
-
195

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 828d ppu 24 2 basic t seriesSinumerik 828d ppu 24 2 basic m seriesSinumerik 828d ppu 240.2 basic mSinumerik 828d ppu 240.2 basic tSinumerik 828d ppu 241.2 basic tSinumerik 828d ppu 241.2 basic m ... Show all

Table of Contents