Anybus
Communicator
- PROFINET Device to PROFIBUS Device
9.1.2. Import Configuration
To easily configure multiple Communicator with the same settings, you can import a configuration file.
Before You Begin
The supported file format is .conf.
Procedure
Figure 39. Files & firmware page
Import configuration file:
1.
On the Files & firmware page, click Import.
2.
In the Import configuration window, click Select file (.conf).
3.
In the Open dialog box, browse to and select the configuration file and click Open.
4.
In the Import configuration window, click Import.
5.
In the Communicator address settings window:
• To import IP settings from the selected configuration file, click Imported settings.
All configuration settings are imported.
• To continue using the current IP settings, click Configured settings.
All configuration settings except the IP settings are imported.
6.
The configuration file is parsed.
• If the configuration is compatible, the settings are imported.
• If any compatibility mismatches occurs, a message about the mismatch appears.
7.
To apply the settings, click Apply in the web-interface header, and follow the instructions.
Page 46 of 60
Configuration File Handling
SCM-1202-202 Version 1.0