Connection of the COMBIVERT R6-N
Housing Size E
- -
- -
++
Figure 13:
4.3.3
Terminals commutation reactor/ harmonic filter
15 / 19Z1B04-1000 (commutation
reactor)
15 / 19Z1C04-1000 (harmonic filter)
L1.1
PE
Figure 14:
30
++
L12
L22
L32
Terminals / earth handle
L.2.1
L3.1
L1.2
L2.2
L3.2
Terminals for commutation reactor / harmonic filter
Name
permissible line cross section
Function
L12
3-phase supply input of
L22
the commutation reactor
L32
++
DC voltage output with
- -
starting current limiting
Connection for shield-
ing/grounding occurs
via provided copper bar
by clamping yoke or
PE,
ring cable lug. It must
be mounted with four
screws at the heat sink.
Strain
The strain relief and the
relief,
shielding must be done
shield-
by the customer e.g.
ing
with two clips.
Name
permissible line cross section
Function
L1.1
L2.1
3-phase mains connection
L3.1
L1.2
PE
Output to COMBIV-
L2.2
ERT R6-N
L3.2
Connection for shield-
PE
ing/earthing
Tightening torque [Nm]
1.5...25 mm²
(AWG 16...4)
-
Tightening torque [Nm]
Size 15
Size 15
1.2...2
2.5...16 mm²
(AWG 20...6)
Size 19
Size 19
2.5...35 mm²
2,5...5
(AWG 12...2)
max.
4
3
3
6