 MS & NS LED
LED status
NS LED
MS LED
Off
Green light
Off
Green light
Red light on
Red light
Red light on
blinking
Red light on Red light on

11.2 Digital Display Diagnosis

Code
0 ~ 63
80
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
DVP-PLC Operation Manual
DeviceNet Network Scanner DVPDNET-SL
Indication
Off
No power
Duplicated ID check has
not completed.
on
MAC ID detection failure
or bus-off
on
No 24V DC power from
DeviceNet network
Hardware error
Indication
Node address of
DVPDNET-SL (in normal
operation)
DVPDNET-SL is in STOP
status.
Duplicated MAC ID check
failure
No slave device in the scan
list.
Low voltage is detected.
Entering test mode
Bus-off
No network power
Internal error; Flash or RAM
check error
Internal error; GPIO check
error
Error produced in factory
manufacturing
Internal error; EEPROM
access failure
Invalid configuration data
How to correct
Make sure that the power supply to
DVPDNET-SL is normal.
Make sure that there is at least one node
which can communicate with DVPDNET-SL
normally, at the same baud rate as
DVPDNET-SL on the network.
1. Ensure that the node address of
DVPDNET-SL is unique.
2. Re-power DVPDNET-SL.
1. Check if the network cable is correctly
connected to DVPDNET-SL.
2. Check the 24V DC network power.
Return to your factory or distributor for repair.
How to correct
--
Turn the PLC to RUN to start I/O data exchange.
1. Ensure that the node address of DVPDNET-SL is
unique.
2. Re-power DVPDNET-SL.
Configure the scan list and download it to
DVPDNET-SL.
Check if the power supply to the DVPDNET-SL and
PLC is normal.
Change IN1of the function switch from On to Off and
re-power the DVPDNET-SL.
1. Check if the network cable connection is proper.
2. Check if the baud rates of the nodes on the network
are consistent.
3. Re-power DVPDNET-SL.
1. Make sure that the cable is correctly connected.
2. Ensure that the power supply to the network is
normal.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
If the error still exists after re-power, send your
DVPDNET-SL back to the factory for repair.
1. Configure the network correctly and re-download it
to DVPDNET-SL.
2. Check if the node address of the slave in the scan
list is the same as the node address of
DVPDNET-SL.
41