DeviceNet Network Scanner DVPDNET-SL
5)
Application example (II)
Control requirement
1> Connection Figure
Note:
Delta DeviceNet slave module, IFD9502 can connect the temperature controller to the DeviceNet network.
2> Parameters setting and devices explanation
 Settings for DVPDNET-SL
Parameter
Node address
Baud rate
 Settings for DNA02
Parameter
Node address
Baud rate
 Settings for VFD-B
Parameter
02-00
02-01
09-00
09-01
09-04
20
M1 = On, set 0x99>>Instance 1>>Attribute 2 of IFD9502 to "0004Hex".
Setting value
00
Set the node address of the DVPDNET-SL to "00".
Set the communication speed of the DVPDNET-SL and bus
500kbps
to "500kbps".
Setting value
02
Set the node address of the DNA02 to "02".
Set the communication speed of the DNA02 and the bus to
500kbps
"500kbps".
Setting value
04
The main frequency is operated on RS-485 interface.
The operation commands are operated on the
03
communication interface. Operation by keys is valid.
01
Communication address of the VFD-B: 01
03
Baud rate: 38,400
03
Modbus RTU mode, data format <8, N, 2>
Explanation
Explanation
Explanation
DVP-PLC Operation Manual