Setup Of Scan Module - Delta DVPDNET-SL Operation Manual

Devicenet network scanner
Table of Contents

Advertisement

4.1.2

Setup of Scan Module

The following dialog is for setting DVPDNET-SL's current mode: master mode or slave mode.
Parameter
Master mode
Scan interval time
Expected Packet Rate
Extension baud rate
Slave mode
Bit-strobed
Polled
Change of State/Cyclic
Mapping
Note: These parameters and the configuration information are downloaded to DVPDNET-SL together.
DVP-PLC Operation Manual
DeviceNet Network Scanner DVPDNET-SL
For setting DVPDNET-SL as master.
The cycle time for master to send and receive the real time data
after real-time data connection is successful.
The result value of the parameter multiplied by 4 is the timeout time.
(Unit: ms)
Master assumes that the slave is offline if it receives no response
from slave after the timeout time is elapsed.
The parameter is effective only when DVPDNET is in master mode.
Selecting "Enable" activates the function.
Select an appropriate baud rate according to actual demand.
For setting DVPDNET-SL as slave
Reserved; no actual purpose now.
The parameter is effective only when DVPDNET is in slave mode.
The filled byte numbers correspond to the data length of outputs and
inputs as DVPDNET-S is in slave mode. "TxSize" corresponds to
"Output length" and "RxSize" corresponds to "Input length".
Reserved; no actual purpose now.
Available for AH models only; no actual purpose now.
Explanation
9