Specifications - Delta DVPDNET-SL Operation Manual

Devicenet network scanner
Table of Contents

Advertisement

DeviceNet Network Scanner DVPDNET-SL
1.3

Specifications

PLC that DVPDNET-SL supports
Item
DVPDNET-SL supports the PLC which can be extendable on its left side
PLC Model
(E.g. DVP-SV, DVP-EH2_L, DVP-SX2, DVP-SA2, DVP10MC11T, DVP-SV3 and
DVP-SX3 and etc.)
 DeviceNet Interface
Item
Transmission
CAN
method
Electrical
500V DC
isolation
Interface
Removable connector (5.08mm)
Transmission
TAP-CB01 cable and TAP-CB02 cable are recommended. (The shielded wire
cable
must be grounded and the cable should be away from the power line)
DeviceNet network provides direct current: 11~25V, 28mA (typical value),
Voltage
125mA impulse current (24 VDC)
 DeviceNet Communication
Item
Explicit connection, IO polled connection, bit-strobe connection, COS/CC
Message type
connection
Standard mode: 125 kbps; 250 kbps; 500 kbps
Baud rate
Extended mode: 10 kbps; 20 kbps; 50 kbps; 125 kbps; 250 kbps; 500 kbps;
800kbps; 1M kbps
Environment
Item
Noise immunity
Operation
Storage
Vibration/shock
resistance
Certificates
2
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2
-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/ IEC 61131-2 & IEC 68-2-27
(TEST Ea)
IEC 61131-2, UL508
Specification