DeviceNet Network Scanner DVPDNET-SL
2.4

Address Switch

The switch is used for setting up the node address of DVPDNET-SL on the DeviceNet network. Range: 00 ~
63 (64 ~ 99 are forbidden).
Switch setting
0 ... 63
64...99
Example:
If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding switch of x10
to 2 and the corresponding switch of x10
Note:
Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
When DVPDNET-SL is operating, changing the setting of node address is invalid.
Use the slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5

Function Switch

The function switches are for:
Setting up the work mode (IN0)
Setting up the baud rate of the DeviceNet network (via DR0 ~ DR1)
DR1
OFF
OFF
ON
ON
IN0
IN1
Note:
 After setting up the function switch is complete, re-power DVPDNET-SL and then the setting is effective.
 Use the slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.
4
Valid DeviceNet node address
Invalid DeviceNet node address
0
DR0
OFF
ON
OFF
Entering the mode of extended baud rate
ON
( see Chapter 9)
When the slave is off-line, the I/O data in
ON
the buffer area will be held.
When the slave is off-line, the I/O data in
OFF
the buffer area will be cleared.
Reserved
Content
to 6.
Baud rate
125kbps
250kbps
500kbps
5
5
DVP-PLC Operation Manual