6 CONNECTION

No.
Function
1
B-
2
B+
3
Start Relay Output
4
Fuel Relay Output
5
Controller Types
6
High Temperature
7
Low Oil Pressure
8
Emergency Stop
9
Remote Start
10
Aux. Transistor
Magnetic Pickup 2
11
(B-) has already connected
with controller innerly.
12
Magnetic Pickup 1
13
N
14
W phase voltage monitor
15
V phase voltage monitor
16
U phase voltage monitor
MGC100 Petrol Genset Controller User Manual
Fig.2 Rear Panel
Table 6 Terminal Connection Description
Cable Size
1.0mm
2
Connected with negative of starter battery.
Connected with negative of starter battery. If wire length
1.0mm
2
is over 30m, better to double wires in parallel. Max. 10A
fuse is recommended.
B+ power is supplied by terminal 2, rated 7A.
1.0mm
2
Connected with start coil of starter.
1.0mm
2
B+ power is supplied by terminal 2, rated 7A.
When this terminal short connected with (B+), it used as
diesel genset controller.
2
1.0mm
When this terminal connected with nothing, it used as
petrol genset controller.
2
1.0mm
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
2
1.0mm
Ground connected is active (B-).
1.0mm
2
Ground connected is active (B-).
1.0mm
2
B- power is supplied by terminal 1, rated 1A.
0.5mm
2
Connected with Rotate Speed Sensor, shielding line is
recommended.
0.5mm
2
1.0mm
2
Connected with N wire.
1.0mm
2
Connected with W phase (2A fuse is recommended).
1.0mm
2
Connected with V phase (2A fuse is recommended).
1.0mm
2
Connected with U phase (2A fuse is recommended).