2. Perform partial proof test 1.
3. Verify the measurement for two temperature points for Sensor 1. Verify the
4. Perform reasonability check of the housing temperature.
5. Restore the loop to full operation.
6. Remove the bypass from the safety PLC or otherwise restore to normal operation.
6.5.3
Comprehensive proof test 3
The comprehensive proof test 3 includes a comprehensive proof test along with a simple
sensor proof test. Reference the FMEDA report for percent of possible DU failures in the
device.
Procedure
1. Bypass the safety PLC or take other appropriate action to avoid a false trip.
2. Perform simple proof test 1.
3. Connect calibrated sensor simulator in place of sensor 1.
4. Verify safety accuracy of 2 temperature points inputs to transmitter.
5. If sensor 2 is used, repeat
6. Restore sensor connections to transmitter.
7. Perform reasonability check of transmitter housing temperature.
8. Perform reasonability check on the sensor(s) values versus an independent estimate
9. Restore loop to full operation.
10. Remove the bypass from the safety PLC or otherwise restore to normal operation.
6.5.4
Inspection
Visual inspection
Special tools
Product repair
The transmitter is repairable by major component replacement.
All failures detected by the transmitter diagnosticsor by the proof-test must be reported.
Feedback can be submitted electronically at Emerson.com/Rosemount/Contact-Us.
6.6

Specifications

The transmitter must be operated according to the functional and performance
specifications provided in the Rosemount 3144P
Failure rate data
The FMEDA report includes failure rates and independent information on generic sensor
models.
Reference Manual
measurement for two temperature points for Sensor 2, if second sensor is present.
(i.e. from direct monitoring of BPCS value) to show current reading is acceptable.
Safety Instrumented Systems (SIS) requirements
Step 3
and
Step
4.
Not required.
Not required.
Product Data
December 2019
Sheet.
201