Temperature (channel 1 and 2)
When the engineering units of the XD_SCALE are selected, this changes the engineering
units of the PRIMARY_VALUE_RANGE in the transducer block to the same units.
This is the only way to change the engineering units in the sensor transducer block,
PRIMARY_VALUE_RANGE PARAMETER.
Configuration examples
Sensor type: 4-wire, Pt 100 α = 385.
Desired measurement process temperature in the –200 to 500 °F range. Monitor the
transmitter electronics temperature in the –40 to 185 °F range.
Transducer block
If host system supports methods:
1. Select Methods.
2. Select Sensor Connections
3. Follow on-screen instruction to setup sensor 1 as a 4-wire, Pt 100 α = 385.
If host system does not support methods:
1. Put transducer block into OOS mode.
2. Go to SENSOR_CONNECTION.
3. Go to SENSOR_TYPE.
(2)
Some choices may not be available due to the current configuration of the device.
Examples:
a) Sensor 2 cannot be configured at all if sensor 1 is set up as a 4-wire sensor.
b) If sensor 2 is configured, Sensor 1 can not be set up as a 4-wire sensor (and vise-versa).
c) When selecting a thermocouple as the sensor type, a 3- or 4-wire connection cannot be selected.
In this situation, configure the other sensor as "Not used." This will clear the dependencies that are preventing the
configuration of the desired sensor.
Reference Manual
°F
K
°R
W
mV
(2)
a. Go to MODE_BLK.TARGET.
b. Select OOS (0 x 80).
a. Select 4-wire (0 x 4).
a. Select PT100A385.
F
OUNDATION
Terminal (body) temperature
°F
K
°R
N/A
N/A
.
Fieldbus Configuration
December 2019
177