Emerson Rosemount 3144P Reference Manual page 167

Temperature transmitter
Hide thumbs Also See for Rosemount 3144P:
Table of Contents

Advertisement

Reference Manual
00809-0100-4021
Alarm type
Out of specification
Failed
Function check
4.9.5
Resource block diagnostics
Block errors
Table 4-2
Table 4-2: Resource Block BLOCK_ERR Messages
Condition name and description
Other
Device Needs Maintenance Now
Memory Failure
Lost NV Data
Device Needs Maintenance Now.
Out of Service
Table 4-3: Resource Block RB.DETAILED_STATUS
RB.DETAILED_STATUS
Sensor Transducer block error
Reference Manual
Active event name
Configuration error
Primary value degraded
Calibration error
Secondary value degraded
Electronics failure
Asic failure
HW/SW incompatible
NV memory failure
Primary value failure
Secondary value failure
Check
lists conditions reported in the BLOCK_ERR parameter.
Description
Active when any SENSOR_DETAILED_STAUS bit is on.
F
Fieldbus Configuration
OUNDATION
Recommended action text string
Re-write the sensor configuration.
Confirm the operating range of the applied
sensor and/or verify the sensor connection
and device environment.e
Retrim the device.
Verify the ambient temperature is within
operating limits.
Replace the device.
Replace the device.
Verify the hardware revision is compatible
with the software revision.
Reset the device then download the device
configuration.
Verify the instrument process is within the
sensor range and/or confirm sensor
configuration and wiring.
Verify sensor range and/or confirm sensor
configuration and wiring.
Transducer Block is under maintenance.
Description
N/A
N/A
A memory failure has occurred in FLASH, RAM,
or EEPROM memory.
Non-volatile data that is stored in non-volatile
memory has been lost.
N/A
The actual mode is out of service.
December 2019
167