Fieldbus Configuration
OUNDATION
December 2019
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the device non-
operational that will cause an alert to be sent. Below is a list of the failures with the highest
priority first.
1. Electronics
2. NV memory
3. HW/SW incompatible
4. Primary value
5. Secondary value
FAILED_MASK
This parameter will mask any of the failed conditions listed in FAILED_ENABLED. A bit on
means that the condition is masked out from alarming and will not be reported.
FAILED_PRI
Designates the alerting priority of the FAILED_ALM, see
and the recommended values are between 8 and 15.
FAILED_ACTIVE
This parameter displays which of the alarms is active. Only the alarm with the highest
priority will be displayed. This priority is not the same as the FAILED_PRI parameter
described above. This priority is hard coded within the device and is not user configurable.
FAILED_ALM
Alarm indicating a failure within a device which makes the device non-operational.
MAINT_ALARMS
A maintenance alarm indicates the device or some part of the device needs maintenance
soon. If the condition is ignored, the device will eventually fail. There are five parameters
associated with MAINT_ALARMS, they are described below.
MAINT_ENABLED
The MAINT_ENABLED parameter contains a list of conditions indicating the device or some
part of the device needs maintenance soon.
Below is a list of the conditions with the highest priority first.
1. Primary value degraded
2. Secondary value degraded
3. Diagnostic
4. Configuration error
5. Calibration error
164
Reference Manual
00809-0100-4021
Process
alarms. The default is 0