Emerson Rosemount 3144P Reference Manual page 174

Temperature transmitter
Hide thumbs Also See for Rosemount 3144P:
Table of Contents

Advertisement

F
Fieldbus Configuration
OUNDATION
December 2019
Primary value 1
status
Bad
Sensor 2 as a default sensor
Primary value 1
status
Good
Good
Good
Uncertain
Uncertain
Uncertain
Bad
Bad
Bad
174
Primary value 2
FEATURE_VAL/
status
FEATURE_STATUS
None (Last good
Bad
value)/Bad
Primary value 2
FEATURE_VAL/
status
FEATURE_STATUS
Primary Value 2/
Good
Good
Primary Value 1/
Uncertain
Good
Primary Value 1/
Bad
Good
Primary Value 2/
Good
Good
Primary Value 2/
Uncertain
Uncertain
Primary Value 1/
Bad
Uncertain
Primary Value 2/
Good
Goode
Primary Value 2/
Uncertain
Uncertain
None (Last good
Bad
value)/Bad
Reference Manual
00809-0100-4021
Recommended action
Hot Backup Active and (Sensor
1 open or short or beyond
operating range) and (Sensor
2 open or short or beyond
operating range).
Recommended action
No error
Hot Backup Active and Sensor
2 out of operating range or
Sensor2 Degraded.e
Hot Backup Active and Sensor
2 Open or short or Beyond
Operating range.
Sensor 1 out of operating
range or Sensor 1 Degraded.
([Sensor 1 out of operating
range or Sensor 1 Degraded]
and [Sensor 2 out of operating
range or Sensor 2 Degraded])
or Drift Alert.
Hot Backup Active and (Sensor
1 out of operating range or
Sensor 1 Degraded) and
(Sensor 2 Open or short or
Beyond operating range).
Sensor 1 open or short or
Beyond operating range.
Sensor 1 open or short or
Beyond operating range and
(Sensor 2 out of operating
range or Sensor 2 Degraded).
Hot Backup Active and (Sensor
1 open or short or beyond
operating range) and (Sensor
2 open or short or beyond
operating range).
Rosemount 3144P

Advertisement

Table of Contents
loading

Table of Contents