Removal Of Compressor - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Outdoor Unit - RK(X)S20/25/35J2V1B
2.7

Removal of Compressor

Procedure
Step
Remove the 2 nuts of
1
the compressor.
Before working, make
sure that the refrigerant is
empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
Heat up the brazed part
2
of the discharge side
and disconnect.
189
Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Discharge side
Warning
Be careful not to get yourself
burnt with pipes and other
parts that are heated by the
gas brazing machine.
Warning
If the refrigerant gas leaks
during work, ventilate the
room. (If the refrigerant gas is
exposed to flames, toxic gas
may be generated.)
Warning
Since it may happen that the
Compressor
refrigerant oil in the
compressor catches fire,
(R11889)
prepare wet cloth so as to
extinguish fire immediately.
Caution
From the viewpoint of global
environment protection, do
not discharge the refrigerant
gas in the atmosphere. Make
sure to collect all the
refrigerant gas.
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four way valve and the
deterioration of the gaskets
affected by heat. (Keep
below 120°C.) For the sake
(R12031)
of this, wrap the four way
valve with wet cloth and
provide water so that the
cloth does not dry.
In case of difficulty with gas
brazing machine
1. Disconnect the brazed part
where is easy to disconnect
and restore.
2. Cut pipes on the main unit
with a tube cutter in order to
make it easy to disconnect.
SiBE041101
Points
Removal Procedure

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents