Indoor Unit; Removal Of Air Filters - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

SiBE041101

1. Indoor Unit

1.1

Removal of Air Filters

Procedure
Step
1. Appearance features
2. Remove the air filters.
1
Hold the both sides of
the front panel, and
open the panel to the
position where it stops.
Slightly push up the
2
center knob of the air
filter and release the
hooks.
3
Pull out the air filter
downward and remove
it.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Signal receiver
ON / OFF button
Room temperature thermistor
Front panel
Dangerous: High voltage
A high voltage is applied to
all the electric circuits of this
product including
thermistors.
(R7900)
Operation lamp
TIMER lamp
INTELLIGENT
EYE lamp
INTELLIGENT
EYE sensor
(R7901)
(R7902)
Air filter
(R7903)

Indoor Unit

Points
Warning
When the signal receiver
catches a signal from the
remote controller, the
receiving tone sounds and
the operation lamp blinks
immediately to confirm the
signal reception.
When the ON/OFF button is
kept pressed for 5 seconds,
the forced cooling operation
is performed for about 15
minutes.
The air filter is not marked
for difference between the
right and left sides.
The air filter can be set
easily by inserting it along
the guides.
Insert the air filter with the
"FRONT"-mark faced up.
Be sure to insert the hooks
(at 2 lower positions) when
mounting the air filter.
134