Unspecified Voltage (Between Indoor Unit And Outdoor Unit) - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

SiBE041101
4.7
Unspecified Voltage (between Indoor Unit and Outdoor
Unit)
UA
Remote
Controller
Display
Method of
The supply power is detected for its requirements (different from pair type and multi type) by the
indoor / outdoor transmission signal.
Malfunction
Detection
Malfunction
The pair type and multi type are interconnected.
Decision
Conditions
Supposed
Causes
Troubleshooting
Check the
indoor
Check the code numbers
(2P01234, for example) of the
indoor and outdoor unit PCB with
the Parts List.
Service Diagnosis
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
combination of the
and outdoor unit.
OK?
YES
Are the
connection wires connected
property?
YES
Matched compatibly?
YES
NO
NO
NO
Troubleshooting
Match the compatible models.
Correct the connection.
Change for the correct PCB.
Replace the indoor unit PCB
(or the outdoor unit PCB).
(R11707)
88

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents