Outdoor Fan System Check; Power Supply Waveforms Check; Inverter Units Refrigerant System Check - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Check
5.7

Outdoor Fan System Check

Check No.09
DC motor
5.8

Power Supply Waveforms Check

Check No.10
Measure the power supply waveform between No. 1 and No. 2 on the terminal board, and check
the waveform disturbance.
Fig.1
5.9

Inverter Units Refrigerant System Check

Check No.11
127
Check the outdoor fan system.
Outdoor fan running?
YES
Outdoor fan
system is
functioning.
Check to see if the power supply waveform is a sine wave. (Fig.1)
Check to see if there is waveform disturbance near the zero cross. (sections circled in Fig.2)
Refrigerant system check
Is the
discharge
pipe thermistor
disconnected from the
holder?
NO
Check for refrigerant leakage.
See the service diagnosis on
refrigerant shortage (U0).
Fan motor
NO
lead wire connector
disconnected?
NO
Go to Check No. 15.
Fig.2
YES
SiBE041101
YES
Reconnect the connector.
(R7159)
Place the thermistor.
Replace the refrigerant.
(R8259)
Service Diagnosis