Program Dry Operation - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Main Functions
1.5

Program Dry Operation

Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
Detail
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in the dry mode with an appropriate capacity for each zone to
maintain the temperature and humidity at a comfortable level.
temperature at start-up
25
Room thermistor
Target temperature
24ºC or more
Room thermistor
temperature at start-up
23.5ºC
18ºC
17.5ºC
Zone C = Thermostat ON
Zone B
Y
Zone A = Thermostat OFF
Thermostat OFF point
X
X
X
18ºC
X
Zone B
SiBE041101
Thermostat ON point
Y
Z
X
0.5ºC
or
2.5ºC
Y + 0.5ºC (zone B)
continues for 10 min.
X
0.5ºC
or
2.0ºC
Y + 0.5ºC (zone B)
continues for 10 min.
X
0.5ºC = 17.5ºC
or
2.0ºC
Y + 0.5ºC (zone B)
continues for 10 min.
X
Z
+0.5ºC
(R11581)
Function and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents