Forced Cooling Operation - Daikin J Series Service Manual

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

SiBE041101

2. Forced Cooling Operation

Conditions
Start
Command
frequency
End
Others
Indoor Unit
Outdoor Unit (20/25/35 class)
Trial Operation and Field Settings
Item
The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced cooling operation is allowed when both the following conditions are
met.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
20/25/35 class: 58 Hz
42 class: 47 Hz
50 class: 66 Hz
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
The protection functions are prior to all others in the forced cooling operation.
Forced Cooling
ON/OFF button (SW1)
2
3
1
Screwdriver
Push here
(R13824)

Forced Cooling Operation

(R14040)
240

Hide quick links: