Daikin J Series Service Manual page 110

Hide thumbs Also See for J Series:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.04
Refer to P.123
Check No.06
Refer to P.125
Check No.11
Refer to P.127
99
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 06
Check the thermistors.
OK
Check No. 04
Check the electronic
expansion valve.
OK
Check No. 11
Check the refrigerant
line.
OK
NG
Discharge pipe thermistor
Outdoor heat exchanger thermistor
Outdoor temperature thermistor
NG
NG
Refrigerant shortage
Four way valve
Water mixed
Stop valve
SiBE041101
Replace the
defective
thermistor.
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R7141)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents