EDUS041016 Power Supply 1. Power Supply Indoor Units Outdoor Units Power Supply FTKN09JEVJU RKN09JEVJU FTKN12JEVJU RKN12JEVJU The Single Split , 208-230V, 60Hz Duct-Free System FTXN09JEVJU RXN09JEVJU FTXN12JEVJU RXN12JEVJU Note: Power Supply Intake ; Outdoor Unit Room Air Conditioners J-Series...
Operation Sound Sound Power Drawing No. 3D066714 3D066715 The data are based on the conditions shown in the table below. Conversion Formulae Cooling Piping Length kcal/h=kW×860 Indoor ; 80°FDB/67°FWB Btu/h=kW×3412 25 ft Outdoor ; 95°FDB/75°FWB cfm=m³/min×35.3 Room Air Conditioners J-Series...
Conversion Formulae The data are based on the conditions shown in the table below. Cooling Heating Piping Length kcal/h=kW×860 Btu/h=kW×3412 Indoor ; 80°FDB/67°FWB Indoor ; 70°FDB/60°FWB 25 ft cfm=m³/min×35.3 Outdoor ; 95°FDB/75°FWB Outdoor ; 47°FDB/43°FWB Room Air Conditioners J-Series...
SERVICE PORT 6-3/32(155) WALL HEIGHT ON AIR OUTLET SIDE MINIMUM SPACE FOR AIR PASSAGE =LESS THAN 47-3/16(1200) GAS STOP VALVE IN CASE OF REMOVING 3/8( φ 9.5)CuT STOP VALVE 1-15/16(50) 1-15/16(50) 1-15/16(50) UNIT = INCH(mm) 3D065923A Room Air Conditioners J-Series...
ON HEAT EXCH. 9/32CuT 9/32CuT CROSS FLOW FAN CROSS FLOW FAN FIELD PIPING FIELD PIPING (1/4CuT) (1/4CuT) FAN MOTOR FAN MOTOR FIELD PIPING 3/8CuT FIELD PIPING 3/8CuT (3/8CuT) (3/8CuT) REFRIGERANT FLOW REFRIGERANT FLOW COOLING COOLING HEATING 4D066315 4D066211 Room Air Conditioners J-Series...
TUBE 2 FILTER PROPELLER FAN 3/8CuT FOUR WAY VALVE ON: HEATING FIELD PIPING (1/4CuT) LIQUID STOP VALVE REFRIGERANT FLOW MUFFLER MUFFLER FIELD PIPING 3/8CuT DISCHARGE PIPE COOLING COMPRESSOR (3/8CuT) THERMISTOR GAS STOP HEATING VALVE ACCUMULATOR 3D066383 Room Air Conditioners J-Series...
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25 ft : Power input (kW) Level difference : 0 ft 6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table. 3D066771 Room Air Conditioners J-Series...
Page 14
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25 ft : Power input (kW) Level difference : 0 ft 6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table. 3D066772 Room Air Conditioners J-Series...
Page 16
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25 ft : Power input (kW) Level difference : 0 ft 6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table. 3D066769 Room Air Conditioners J-Series...
Page 18
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25 ft : Power input (kW) Level difference : 0 ft 6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table. 3D066770 Room Air Conditioners J-Series...
<--- line : heating capacity> R-410A (09/12 class) Range of the refrigerant additional charge 16.4 32.8 49.2 Piping length (ft) (R11493) Note: The graph shows the factor when additional refrigerant of the proper quantity is charged. Room Air Conditioners J-Series...
Heating Cooling 114.8 57.2 73.4 82.4 (5˚FDB) Indoor temp. (˚FWB) Notes: Indoor temp. (˚FDB) The graphs are based on the following conditions. • Equivalent piping length 25ft • Level difference 3D066174A • Air flow rate High Room Air Conditioners J-Series...
2. The data are based on the conditions shown in the table 3.3 ft below. (R5162) Outdoor Unit 3.3 ft (R4796) Cooling Heating Piping Length Indoor ; 80°FDB/67°FWB Indoor ; 70°FDB/60°FWB 25 ft Outdoor ; 95°FDB/75°FWB Outdoor ; 47°FDB/43°FWB Room Air Conditioners J-Series...
60Hz 208/230V(L) Cooling Heating NC-10 NC-10 APPROXIMATE APPROXIMATE THRESHOLD HEARING THRESHOLD HEARING FOR CONTINUOUS FOR CONTINUOUS NOISE NOISE 3D066745 1000 2000 4000 8000 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) Room Air Conditioners J-Series...
Page 23
NC-30 Cooling Heating NC-20 NC-20 APPROXIMATE APPROXIMATE THRESHOLD HEARING THRESHOLD HEARING FOR CONTINUOUS FOR CONTINUOUS NOISE NOISE 3D066751 1000 2000 4000 8000 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) OCTAVE BAND CENTER FREQUENCY (Hz) Room Air Conditioners J-Series...
(This unit uses an inverter, which means that it must be use a ground leak detector capable handling high harmonics in order to : INDOOR FAN MOTOR prevent malfunctioning of the ground leak detector itself.) : FULL LOAD AMPS (A) : FAN MOTOR RATED OUTPUT (W) 3D066179C Room Air Conditioners J-Series...
Packing materials such as nails and refrigerant circuit can cause an abnormal pressure other metal or wood parts, including plastic packing rise or rupture, resulting in injury. Room Air Conditioners J-Series...
Page 26
(inverter or rapid start types). parts other than those specified by Daikin are used, Install the indoor unit far away from fluorescent lamps fire or explosion may occur.
9) no laundry equipment is located. Wireless remote controller 1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly received by the indoor unit (within 23 feet (7m)). Room Air Conditioners J-Series...
1) In the same way as when connecting to an HA system, remove the metal plate electrical wiring cover. 2) Cut the address jumper (JA) on the printed circuit board. ADDRESS EXIST 3) Cut the address jumper (J4) in the remote controller. ADDRESS EXIST Room Air Conditioners J-Series...
Page 29
Wireless photocatalytic make sure that control remote air-purifying filter signals are properly controller received by indoor unit. Fixing screw for remote Remote controller holder controller holder 1/8” × 13/16” (M3 × 20mm) Room Air Conditioners J-Series...
(160) (54) φ2-9/16 (φ65) 13-1/64 13-1/32 (330.5) (331) 30-5/16 (770) Drain hose unit: inch (mm) position * The removed pipe port cover can be Removed pipe kept in the mounting plate pocket. port cover Mounting plate Room Air Conditioners J-Series...
6) Press the bottom frame of the indoor unit with both hands to set of wires with insulating tape. it on the mounting plate hooks. Make sure the wires do not catch on the edge of the indoor unit. Room Air Conditioners J-Series...
• Insert the drain hose to this depth so it won’t be pulled out of the drain pipe. hose to this depth so it won’t be pulled out of drain pipe. 1-15/16” (50mm) Drain hose or more Vinyl chloride drain pipe Outer wall (VP-30) Room Air Conditioners J-Series...
Page 33
* 5-4.Remove the indoor unit electrical component box. 1) Remove the louver. 2) Disconnect the communication wiring. 3) Disconnect the connector (S200). 4) Remove the thermistor from the heat exchanger. 5) Remove the electrical component box installation screw (1 screw). Disengage the tab. Room Air Conditioners J-Series...
Page 34
Figure 3: Installing the accessory Cut-outs for the connection cords Install the accessory cover Install the accessory. in its original position. Accessory cover Cut-out for the “S403” connection Cut-out for the connection cord Accessory Room Air Conditioners J-Series...
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit. • Never install a drier to this R410A unit in order to guarantee its lifetime. • The drying material may dissolve and damage the system. • Incomplete flaring may cause refrigerant gas leakage. Room Air Conditioners J-Series...
O.D. 1/4 inch (6.4mm) (12-15mm) (8-10mm) Minimum bend radius Thickness 0.393 inch (10mm) Min. 1-3/16 inch (30mm) or more Thickness 0.031 inch (0.8mm) (C1220T-O) 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes. Room Air Conditioners J-Series...
Page 37
The specified wires are used for inter-unit wiring connections. Inoperative or burn damage Indoor or outdoor unit’s air inlet or air outlet has clear path of air. Incomplete cooling/heating Stop valves are opened. function Indoor unit properly receives remote control commands. Inoperative 3P253189-1B Room Air Conditioners J-Series...
Daikin are used, • Only qualified personnel must carry out the installation fire or explosion may occur.
Page 39
• Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). Install the indoor unit far away from fluorescent lamps as much as possible. Room Air Conditioners J-Series...
• To prevent exposure to wind, it is recommended to install a baffle plate on the air discharge side of the outdoor unit. • In heavy snowfall areas, select an installation site where the snow will not affect the unit. Room Air Conditioners J-Series...
Adjust foot height until the unit is leveled. Otherwise, water Where there is a danger of the unit leakage or pooling of water may falling, use foot bolts, or wires. occur. unit: inch (mm) Room Air Conditioners J-Series...
1-1/4 inch (30mm) in height under the outdoor Drain plug unit’s feet. Hose (available commercially, 3) In cold areas, do not use a drain hose with the outdoor unit. inner dia. 5/8 inch (16mm)) (Otherwise, drain water may freeze, impairing heating performance.) Room Air Conditioners J-Series...
1/4 inch (6.4mm) 15.9-20.2ft lbf 15.9-20.2ft lbf 24.1-29.4ft lbf • 10.4-12.7ft lbf • • • (21.6-27.4N m) • (21.6-27.4N m) • (32.7-39.9N m) • (14.2-17.2N m) • Service port cap 7.9-10.8ft lbf • tightening torque (10.8-14.7N m) • Room Air Conditioners J-Series...
*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4). Room Air Conditioners J-Series...
Thickness 0.393 inch (10mm) Min. Gas pipe Liquid pipe insulation insulation 1-3/16 inch (30mm) or more Finishing tape Drain hose Thickness 0.031 inch (0.8mm) (C1220T-O) 3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes. Room Air Conditioners J-Series...
• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock. • After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced operation. Room Air Conditioners J-Series...
Page 47
In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction. Place the round crimp-style terminals on the wires up to the covered part and secure in place. Room Air Conditioners J-Series...
Page 48
Good Wrong Stripping wire at terminal block 3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop. Room Air Conditioners J-Series...
Page 49
The specified wires are used for inter-unit wiring connections. Inoperative or burn damage Indoor or outdoor unit’s air inlet or air outlet has clear path of air. Incomplete cooling/heating Stop valves are opened. function Indoor unit properly receives remote control commands. Inoperative 3P253189-4B Room Air Conditioners J-Series...
Meanings of DANGER, WARNING, CAUTION, and NOTE leakage, electric shock, and fire. Only use Symbols: accessories made by Daikin that are specifically designed for use with the equipment and have them installed by a professional. DANGER ....Indicates an imminently hazardous situation which, if not avoided, will •...
Page 51
• Do not touch the air inlet or aluminum fin of the air work unless you are licensed to do so. Consult with conditioner as they can cut and cause injury. your dealer for electrical work and grounding work. Room Air Conditioners J-Series...
Page 52
• Make sure that there are no obstacles close to the and water leakage from the indoor unit may occur. outside unit. Obstacles close to the outside unit may Stop operating the air conditioner and contact your dealer. Room Air Conditioners J-Series...
Remote Controller Loss Prevention with Chain KKF910A4 2 Standard accessory 1 An interface adaptor (KRP980B1) and a cord (BRCW901A03 or BRCW901A08) are necessary. 13.1.2 Outdoor Units Option Name RKN09/12JEVJU RXN09/12JEVJU Drain Plug — KKP937A4 Air Direction Adjustment Grille KPW937A4 Room Air Conditioners J-Series...
Secure the remote controller lower case with the two supplied machine screws. KJB2121A KJB1111A Switch box (Field supplied parts) Machine screws (M4 x 16) For the field supplied switch box, use optional accessories KJB1111A or KJB2121A. Room Air Conditioners J-Series...
Page 80
(Remote controller cord 4 wire) 5. Temperature indication change To change from Celsius temperature indication to Fahrenheit one Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated. ← See Operation Manual 3P202923-2B Room Air Conditioners J-Series...
Page 81
Sets the current time and timer. Adjusts the temperature setting. CAUTION •This remote controller cannot be used together with a standard wireless remote controller. Otherwise, what appears on this remote controller's display may fail to correspond to actual operating conditions. Room Air Conditioners J-Series...
Room temp. Less than 80% Indoor humidity two weeks as required) or so. -15 to 20 ˚C (5˚F to 68˚F) Outdoor temp. Heating Less than 27 ˚C Room temp. Operation limit differ according to the model. Room Air Conditioners J-Series...
Page 83
19˚C (66˚F). In this case, no change by the temperature indication change is observed. When the temperature indication change is set, the preset temperature is transmitted to the indoor unit so that the reception sound will be heard from the indoor unit. Room Air Conditioners J-Series...
Page 84
Note While running in the DRY mode, you may feel cool or warm air from the air outlet. In this case, readjust the airflow direction with the vertical airflow direction louvers. (except Duct Connected type) Room Air Conditioners J-Series...
Page 85
Since the air conditioner heats the whole room by circulating hot air, it takes some time to heat the entire room completely. Room Air Conditioners J-Series...
This will enhance the cooling and heating effect. On the air conditioners with vertical and horizontal swing function, be sure to adjust the airflow directions using the remote controller. Do not forcibly adjust louvers by hand or a malfunction may occur. Room Air Conditioners J-Series...
Page 87
This function cannot be used. Note The operating procedure and remote controller display are different depending on the indoor unit being connected. Read How to Adjust the Airflow Direction in the air conditioner’s Operation Manual. Room Air Conditioners J-Series...
If one minute has passed before making any timer setting, the previous timer settings are reintroduced and the timer is on standby. In this case, use the (time setting) button and make your desired timer settings. Room Air Conditioners J-Series...
Page 89
The circuit breaker has been programmed. and system starts. and system stops. The set time is The ON timer setting The timer setting no activated. displayed. no longer displays. longer displays. The power fails. Room Air Conditioners J-Series...
Page 90
Example of display with DAILY timer programmed Note The system starts and stops repeatedly until the DAILY timer is set off. Before you leave home for a Timers Timer alone long time, set the DAILY timer off. programmed. programmed. Room Air Conditioners J-Series...
The 24-hour timer display The 24-hour timer display is blinking. is blinking. This means that Timers This means that the timer has not been programmed for the same time settings. programmed yet. New time settings must be made. Room Air Conditioners J-Series...
R un the system when the room temperature is below 28˚C (82˚F). Finally turn off the circuit breaker dedicated for the room air conditioner. Clean the air filter and place it back into position. 3P202922-2B Room Air Conditioners J-Series...
Flap (in control of wind Electrical directions upward component box and downward) S403 Mounting position PCB of indoor unit of the set Note: Wires indicated by thick lines are not provided to the set. Room Air Conditioners J-Series...
Page 94
1) Push up. of the front grille, and while hooks (3 locations). pushing up, pull it toward you. 2)Install 2screws of the front grille. 3)Install the air filter and then mount the front panel. 2) Pull toward you. Room Air Conditioners J-Series...
Position of each Fig. 2 connector Fig. 3 Position of thermistor S200 Thermistor Communication wiring Make sure that the mounting bracket Mounting screw of electrical Flap of the thermistor will not fall off. component box Room Air Conditioners J-Series...
Page 96
Place the connection cord to come in contact with the protruding part. Connection cord Protruding part Fit in. Electrical component Routing connection cord Push the electrical component until it snaps into engagement with the tab. S403 connection cord Connection cord 3P214218-1 Room Air Conditioners J-Series...
Grille grating Grille grating outdoor unit. 3.Be advised that if the fan direction is up, dead leaves and other foreign matter easily accumulates in the exhaust vent. Prepared hole Prepared hole 4P104499-1A Room Air Conditioners J-Series...
Page 98
AMERICAS 1645 Wallace Drive, Suite 110 Carrollton, TX75006 info@daikinac.com www.daikinac.com Specifications, designs and other content appearing in this brochure are current as of April 2010 but subject to change without notice. EDUS041016 Printed in U.S.A. 04/2010 B AK...