10

CC-Link Code Numbers

 Command Codes
Command Code
1181H
Read Run command source
1180H
Read frequency reference source
2181H
Write Run command source
2180H
Write frequency reference source
0074H
Fault History 1
0075H
Fault History 2
0076H
Fault History 3
0077H
Fault History 4
0078H
Fault History 5
0079H
Fault History 6
007AH
Fault History 7
0080H
Fault History 8
0081H
Fault History 9
0082H
Fault History 10
006DH
Read frequency reference (RAM)
006EH
Read frequency reference (EEPROM)
007BH
Read LOCAL/REMOTE status
00FBH
Write LOCAL/REMOTE status
00EDH
Write frequency reference (RAM)
00EEH
Write frequency reference (EEPROM)
Read parameters
Parameter settings
00F4H
Clear all fault contents
00FDH
Reset drive
YASKAWA ELECTRIC SIEP C730600 22C V1000 Option CC-Link Technical Manual
Table 20 Command Codes
Name
0: LED operator
1: Control circuit terminals (sequencer input)
2: MEMOBUS communications
3: Option unit
0: LED operator
1: Control circuit terminals (analog input)
2: MEMOBUS communications
3: Option unit
4: Pulse train input
0: LED operator
1: Control circuit terminals (sequencer input)
2: MEMOBUS communications
3: Option unit
0: LED operator
1: Control circuit terminals (analog input)
2: MEMOBUS communications
3: Option unit
4: Pulse train input
Reads the contents from U3-01.
Reads the contents from U3-02.
Reads the contents from U3-03.
Reads the contents from U3-04.
Reads the contents from U3-05.
Reads the contents from U3-06.
Reads the contents from U3-07.
Reads the contents from U3-08.
Reads the contents from U3-09.
Reads the contents from U3-10.
Reads the drive's frequency reference from RAM.
Reads the frequency reference from EEPROM.
0: 0 = Frequency reference is supplied by CC-Link.
1: 0 = FWD/REV Run command is supplied by CC-Link.
8: 1 = During Stall Prevention.
0: 0 = Frequency reference from CC-Link is enabled.
1: 0 = FWD/REV Run command from CC-Link is enabled.
When power is cycled, however, the source is determined by parameters b1-01 and b1-02.
If one of the multi-function relay input terminals is set to switch the source of the Run command (H1- = 2),
then the Run command and frequency reference will be supplied by parameters b1-01 and b1-02 when that
terminal is open, and parameters b1-15 and b1-16 when that terminal is closed.
Writes the frequency reference for the drive to RAM.
Writes the frequency reference and all parameter values to EEPROM.
Adds 1000H to the MEMOBUS register number.
Master executes commands by adding 2000H to the MEMOBUS register number. Conversion takes place on the
option unit side.
9696H: Clear fault history
9696H: Fault reset
10 CC-Link Code Numbers
Description
29