 Grounding Method Switch
The grounding method switch (S1) can change the grounding method for the CC-Link Option between common grounding and independent
grounding. Refer to
Setting Grounding Method Switch on page 13
Note: The grounding method switch (S1) is only available for CC-Link Options REV.B and later. Check the REV version printed on the nameplate of your CC-Link Option.
Grounding Method Switch (S1)
S1
NC
FE
Figure 5
Figure 6
 CC-Link Option LED Display
Name
Color
L.RUN
Green
L.ERR
SD
RD
 Setting Station Address
Set drive parameter F6-10 to a station address (Range 1 to 64) unique to the network. If set to 0, the L.ERR light will turn on and a Station Address
Error (AEr) will occur.
YASKAWA ELECTRIC SIEP C730600 22C V1000 Option CC-Link Technical Manual
to change the grounding method.
Table 4 Details on the Grounding Method Switch
Terminal Name
Changes the grounding method for the CC-Link Option between common
FE
grounding and independent grounding.
Figure 6 Independent Grounding
Table 5 CC-Link Operation LED Status
Indication
Status
ON
Normal operation
OFF
Timed out
ON
CRC error
Red
OFF
During communications
ON
Sending data
Red
OFF
No data transfer
ON
Detecting data received
Red
OFF
Waiting for data
Function
CC-Link
Drive
Option
Ground to
100  or less
Figure 5 Common Grounding
CC-Link
Drive
Option
Ground to
100  or less
Operating Status
• Receiving data normally
• Timed out waiting to receive
• Logging onto the network
• During reset
• CRC error
• Station address setting error (F6-10 = 0)
• Normal communications
• During reset
• Sending data
Note: LED may appear to flash with slower baud rates.
• No data being sent
• During reset
• Detecting data that was received
Note: LED may appear to flash with slower baud rates.
• Data not yet received
• During reset
4 CC-Link Option Components
Default
FE (common grounding)
Remarks
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac drive-v1000 option cc-link

Table of Contents