Drive → PLC
Device
Signal Name
RX0
Forward Run
RX1
Reverse Run
RX2
Terminals MA, MB, MC Function
RX3
Speed Agree
RX4
During Stall Prevention
RX5
During Undervoltage
RX6
Terminal P1 Function
RX7
Terminal P2 Function
RX8, 9
Reserved
RXA
CC-Link Option Fault
RXB
Monitoring Motor Revolutions
RXC
Obtain Monitor Data
RXD
Frequency Setting Ready 1
RXE
Frequency Setting Ready 2
RXF
Command Code Execute Complete
RX10
Reserved
to 19
RX1A
Error
RX1B
Remote Station Ready
RX1C to 1F
Reserved
Note: If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2 flag) too often can shorten the
performance life of the drive's internal memory.
 Remote Register
PLC → Drive
Remote
Name
Register
RW
Monitor Code
W0
RW
Frequency Setting
W1
RW
Command Code
W2
RW
Write Data
W3
<1> Refrain from saving data to the EEPROM excessively because the EEPROM used in the drive can only be written to 100,000 times.
YASKAWA ELECTRIC SIEP C730600 22C V1000 Option CC-Link Technical Manual
Table 12 Remote I/O Table (Drive → PLC)
ON: Forward Run Command Present (includes DC Injection Braking)
OFF: No Forward Run Command
ON: Reverse Run Command Present
OFF: No Reverse Run Command (includes DC Injection Braking)
Multi-function output: H2-01
ON: Output frequency is between frequency reference and the detection width set to L4-02.
Multi-function output: H2-02
Multi-function output: H2-03
Comm. error between drive and CC-Link device
ON: Currently monitoring motor revolutions.
ON: Monitor data has been updated.
ON: Displays the main frequency reference that has been set.
ON: Displays the data set to d1-01 (Frequency Reference 1).
Note: Also sets the main frequency reference at the same time.
ON: Displayed after the specified command code has been executed.
RXF signal switches off when the RYF command is no longer present.
ON: Fault occurred on the drive side.
ON: Drive is ready to operate.
Table 13 Remote Register (PLC → Drive)
• Sets the code number of the items to be displayed by the monitor. (Refer to
• Once the monitor code has been set, the monitor value is stored in register RW
monitor execute request flag).
• While RW
is updated, RXC (during monitor flag) remains on.
R0
• Specifies the source of the frequency reference. The value set to this register becomes the main frequency
reference whenever RYD (frequency setting reference 1) is enabled.
• When RYE (frequency setting reference 2 flag) is enabled, then the value for frequency reference 1 is
written and saved to EEPROM
.
<1>
Note: Parameter o1-03 determines the setting units for the frequency reference.
• Sets the command code to execute functions such as the fault reset, fault history, parameter read, and so on.
(Refer to
Command Codes on page
• When RYF (command code execution request flag) is enabled, the drive executes the specified command.
Once the command has been carried out, RXF switches on.
Note: The value set to RW
(write data) should be adjusted accordingly to match changes to
W3
any parameter settings.
• Sets the value to be used along with RW
• RYF (command code execution request flag) needs to be enabled after the command code and write data
have been set.
Description
Description
29,
Extended Command Codes on page
(Command Code) as needed.
W2
8 CC-Link Data Table
Monitor Codes on page
31).
by enabling RYC (the
R0
RYC (Monitor Execute Request)
• RYD (Frequency Reference 1)
• RYE (Frequency Reference 2)
30.)
RYF (Command Code Execute
Request)
Default
(H2-01 = E: Fault)
(H2-02 = 0: During Run)
(H2-03 = 2: Speed Agree 1)
Data is stored in remote register
RW
.
R1
Request Flag
23