Typical Vent Installation - Valor RetroFire RF24JDN Installation Manual

Direct vent gas
Table of Contents

Advertisement

Co-Axial with RA24CA

Typical Vent Installation

See Approved Venting Components on page 40 of this
manual.
Vent Location
The vent terminal must be located throught the roof.
This direct vent appliance is designed to operate when
an undisturbed airflow hits the outside vent terminal
from any direction.
Check local codes for allowable vertical vent
termination.
Venting Table
Maximum
40 ft (measured to bottom of termination)
vertical height
Minimum
8 ft (measured to bottom of termination
vertical height
Maximum
4 ft (measured center to center of pipe
horizontal run
Maximum
45° (sweeping bend to allow for obstructions)
off set angle
Venting Notes
Where possible, avoid splicing flex pipes.
Four feet horizontal is permissible to allow for routing
around masonry projections. Do not bend flex pipe
over a 45 degrees radius.
• Flex liners may only be installed into solid-fule burn-
ing fi replaces and chimney systems (no combustible
constructions).
• The appliance must not be connected to a chimney
fl ue serving a separate solid-fuel burning appliance.
Typical Vent Installation
Terminal Cap (co-axial)
Terminal Adapter with
Flashing included in
590FVK2
5 x 3" flex liners—
see Venting Table
for length allowed
5 x 3" Liners
5" min.
Bend
Radius
RF24J
Co-axial applications (using RA24CA Vent Plate)
NOTE
Co-linear or co-axial flexible aluminum venting
liners should be professionally inspected
periodically for corrosion and damage and
replaced when necessary. If the installation does
not allow for future inspection or replacement of
the flexible aluminum liners, then stainless steel
vent liners are recommended.
17