Vent Termination

Co-Linear—3" x 3" fl ex
Existing Square Chimneys
559CLT—Co-Linear Terminal and 559FSK—Square
Flashing Kit are recommended—see list of approved
venting accessories on page page 40 for alternate
venting components.
1. Cut fl ashing kit to size. Allow extra around perim-
eter for drip edge to be formed on site.
2. Seal fl ashing to top of chimney using sealent (not
supplied).
3. Fasten terminal to fl ashing using sheet metal
screws as shown.
Existing Round Factory-Built Chimneys
The 559CLT terminal is designed to fit existing 7" or
8" diameter factory-built round chimneys without
requiring additional flashing. Ensure the installation
of the terminal seals off the top of the chimney space
to avoid convective air loss. The diagrams below
show a typical terminal installation for an 8"
diameter air-cooled chimney system.
Sidewall Termination, ONLY with Valor 720SWK
See instructions provided with kit.
Existing Air-Cooled Chimney
(Factory-Built Fireplaces)
Install 2 - 3" dia.
Flex Liners
Identify
which
Liner is
Exhaust
10" dia.
7-5/8" dia.
559CLT
559CLT + 559FSK
720SWK—Sidewall terminal—with RA24-CL ONLY
Remove Top
Portion of
Terminal
Connect Liners to
Corresponding
Collar on Terminal
using Sheet Metal
Screws (longer
collar is exhaust
collar)
Vent Termination
10"
11"
559SFK Flashing
(cut to required
size and form
drip edge on site)
Front
3"
intake
Maintain Air-Cooled
Function of Existing
Chimney System
Fasten Terminal
to Flashing
(3 locations)
Ensure Flashing
Remains over
Air-Cooled
Openings
559CLT Terminal
Fasten to Flashing
with Sheet Metal
Screws (3 locations)
2 - 3" Flex Liners
Rear
3"
exhaust
559CLT Termination
Ensure Exhaust
Portion of Chimney
is Sealed at Top