[Pr. PF18_STO diagnosis error detection time (**STOD)]

Initial value
10 [s]
Set the time from when the error of the STO input or STO circuit is detected until the occurrence of [AL. 068.1 STO signal
mismatch error].
When "0" is set, [AL. 068.1] is not detected.
The safety level depends on the setting value of this servo parameter and whether STO input diagnosis is performed by TOFB
output as shown in the following table.
Setting value
0
1 to 60
When the STO function is not used with the short-circuit connector connected to the CN8 connector, the safety level does not
change even after setting this servo parameter.
[Pr. PF19_Friction failure prediction - Compensation coefficient 1
(TSL)]
Initial value
0 [0.0001 %/°C]
Set compensation coefficient 1 to compensate the dynamic friction being used for the friction failure prediction.
When the friction failure prediction warning selection is set to the automatic threshold setting, the value will be calculated
automatically from the estimated dynamic friction.
When performing threshold manual setting on an equipment for which the threshold setting has been made once, set the
value that has been calculated by the threshold automatic setting.
Setting this servo parameter decreases the possibility of erroneous detection of friction failure prediction, even with the
manual threshold setting.
[Pr. PF20_Friction failure prediction - Compensation coefficient 2
(TIC)]
Initial value
0 [0.1 %]
Set compensation coefficient 2 to compensate the dynamic friction being used for the friction failure prediction.
When the friction failure prediction warning selection is set to the automatic threshold setting, the value will be calculated
automatically from the estimated dynamic friction.
When performing threshold manual setting on an equipment for which the threshold setting has been made once, set the
value that has been calculated by the threshold automatic setting.
Setting this servo parameter decreases the possibility of erroneous detection of friction failure prediction, even with the
manual threshold setting.
1 SERVO PARAMETER DETAILS
92
1.7 Extension setting 3 servo parameters group ([Pr. PF_ _ ])
Setting range
0 to 60
STO input diagnosis by TOFB
output
Execute
Do not execute
Execute
Do not execute
Setting range
-32768 to 32767
Setting range
-10000 to 10000
Setting method
Common
Safety level
EN ISO 13849-1:2015 Category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2,
and EN 61800-5-2 SIL 2
EN ISO 13849-1:2015 Category 3 PL e, IEC 61508 SIL 3, EN 62061 SIL CL 3,
and EN 61800-5-2 SIL 3
EN ISO 13849-1:2015 Category 3 PL d, IEC 61508 SIL 2, and EN 62061 SIL
CL 2
Setting method
Each axis
Setting method
Each axis
Ver.
C4
Ver.
C4
Ver.
C4