7.7.4 Load non-safety parameters from the FC

All non-safe parameters are loaded to the drive.
Preconditions:
A valid FC must be inserted in the socket M1.
A valid configuration must be present on the FC.
The drive must be powered up or rebooted with the inserted M1.
If no FC is inserted, the drive ignores the command and starts up normally.
Steps
1
2
3
4
5a
No error
5b
Error

Table 35: Load non-safe parameters from the FC

0185-1174_E_1V1_SM_C1251-2S / 2021-11-26 16:43 (Rev. 12500)
Description
Set ID switches S1/S2 to FCh.
Power cycle the drive.
Wait until LEDs L3 and L4 blink together red and green with ca. 4 Hz.
If the drive starts up normally, no flash card is detected.
Set ID switches S1/S2 to 22h.
The blinking stops.
The drive safes the configuration and boots automatically.
Wait until the drive has booted completely.
In case of an error, the L3 and Error LEDs are alternating blinking at ca. 2 Hz.
Possible errors:
The flash card is not compatible (no LinMot-Card, wrong type, ...).
The flash card is not writable.
The flash Card is removed during operation.
Configuration file is not readable.
Configuration is not compatible (HW and FW version).
Required action:
Reboot or power cycle the drive
Check the error cause