8. TROUBLESHOOTING
Troubleshooting of this sample screen is explained below.
8.1 Troubleshooting Related to GOTs
(1) System alarm "535 Cannot open image file." occurs.
No.
The specified file does not exist in the
1
drive.
(2) System alarm "402 Communication timeout. Confirm communication pathway or modules." occurs.
No.
Cannot access to the PLC CPU module
1
or the Ethernet module.
Cause
Cause
The image file is not stored. Check that there is no problem
in the communication with the camera recorder module.
• Check that the cables between the GOT and the PLC CPU
module or the Ethernet module are not disconnected.
• Check the connection status to the HUB.
• Check that GOT Ethernet Setting is correct.
56/59
Countermeasure
Countermeasure