Table: CAN register list
AsciiToHex(FF)
Table: CAN or RS-232/RS-485/RS-422/USB FIFO overflow flag list
AsciiToHex(O)
 Example:
Command: S<CR>
Receive: !50000000<CR>
Obtain some current information on the I-7530 module. The response will show the following
results: CAN baud rate=250K, CAN register= normal, CAN transmit error counter=0, CAN
receive error counter=0 and CAN/RS232 FIFO= normal.
I-7530, I-7530-FT, I-7530A, I-7565, tM-7530, tM-7530A, tM-7565 User Manual Version 1.5
Copyright © 2018 ICP DAS Co., Ltd. All Rights Reserved
Bit 7
Bus Off Mode
Bit 6
Error Passive Mode
Bit 5
Reserved
I-7530 series: Overrun Buffer
Bit 4
tM-7530/tM-7530A/tM-7565: Reserved
Bit 3
Stuff Error General
Bit 2
CRC Error General
Bit 1
Form Error General
Bit 0
Acknowledgment Error General
Bit 3
Reserved
Bit 2
Reserved
Bit 1
RS-232/RS-485/RS-422/USB FIFO Overflow
Bit 0
CAN FIFO Overflow
Description
Description