15.2.2 Setting the ignition electrode
- Check the setting of the ignition electrode. Set the gap between the
ignition electrodes: 3 to 4 mm.
15.2.3 Checking the hydraulic pressure
The hydraulic pressure must be a minimum of 0.8 bars. We
recommend filling the installation to around 1.5 bars higher than the
static height.
15.2.4 Checking the ionization current
Tilt the flap on the control panel.
Press key
and
Use keys + and - to switch from
-
: Maximum boiler output
-
: Minimum output
15/02/2011 - 300014279-001-J
simultaneously for 2 seconds.
to
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
In the display area:
EMISSION MES. 88.8°: Boiler temperature
EMISSION MES. 8888: Fan speed
EMISSION MES. 88.8uA: Ionization current
15. Maintenance