Specific Maintenance Operations; Replacing The Ionization/Ignition Electrode - DeDietrich Innovens MCA 35 Installation And Service Manual

Wall-hung gas condensing boilers
Hide thumbs Also See for Innovens MCA 35:
Table of Contents

Advertisement

7. Checking and maintenance
7.5

Specific maintenance operations

2
1
100
If the standard inspection and maintenance operations have revealed
the necessity to carry out additional maintenance work, proceed as
follows, depending on the nature of the work:
7.5.1.
Replace the ionization/ignition electrode in the following cases:
4 Ionization current <3 µA.
4 Electrode worn.
If replacement is necessary, proceed as follows:
1. Remove the cable from the ionization/ignition electrode on the
3
ignition transformer.
2. Unscrew the 2 screws and remove the ionization/ignition
electrode.
3. Replace the ionization/ignition electrode.
T001528-A

Replacing the ionization/ignition electrode

MCA 35
15/06/12 - 300022160-001-01