Messages - Alarms; Faults - DeDietrich DTGE130-35 Eco.NOxPlus Technical Instructions

Gas fired condensing boiler
Table of Contents

Advertisement

10. Messages - Alarms

10 Messages - Alarms

10.1 Faults

In the event of a fault, the display may show the following messages. Contact your fitter.
Message
The message SHOW REM.CTRL
SHOW REM. CTRL
indicates the presence of an override on
a remote control
REVISION
Boiler service required
24V SHORT-CIRC.
Short circuit 24 V
Faults
BURNER FAILURE
Igniter fault
Ionization fault
Gas valve defective
No gas or presence of air in the pipe
I-CURRENT FAIL
Ionization fault during operation
MCBA FAILURE XX
Internal safety control box fault
MCBA FAILURE 5
External influences
MCBA FAILURE 11
Internal fault
DEF.MCBA 24
Boiler reversal sensor and return sensor Reverse the sensors
VALVE FAIL
Combined gas valve unit defective
REARM CVI
Control error
MCBA.COM.FAULT
Communication error between
DIEMATIC and safety control box
BOILER S.FAIL.
The corresponding sensor is off or
BACK S.FAILURE
short-circuited
OUTSI. S.FAIL.
DHW S. FAILURE
OUTL S.B FAIL.
OUTL S.C FAIL.
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
SMOKE S. FAIL.
SWIM.P. S.FAIL
ST.TANK S.FAIL
44
Probable causes
To cancel the overrides on all remote controls, press the AUTO key for 5 seconds.
Contact the professional responsible for maintenance of the boiler.
Check the wiring.
Probable causes
Check the ignition electrode (spacing of the electrodes), its connector and its connection
cable
Check the earth
Replace the gas valve
Measure the gas supply pressure
Check the earth
Reset the boiler
switch
Check the wiring
Check that multi-wire connections are undamaged
panel
The safety control box does not signal a gas valve
- The wiring of the gas valve;
- The gas valve could be defective (coil defective)
Reset the boiler
Check the link and the connections between DIEMATIC and safety control box
the boiler
Check the link and the connectors
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
.
.
Replace if necessary
.
Check the ionization current
.
.
Bleed the gas circuit
.
Check the ionization current
.
Briefly cut the electrical power supply to the boiler using the On/Off
.
Replace the command and safety box
.
.
Eliminate electro-magnetic influences
.
Pump incorrectly fitted
.
.
Briefly cut the electrical power supply to the boiler using the On/Off switch
.
Replace the sensor if necessary
Action
Action
.
If necessary rectify the level of CO
.
.
If necessary rectify the level of CO
.
.
Presence of humidity in the control
.
.
.
:
Check
.
.
15/02/2011 - 300014279-001-J
.
2
.
2
.
Reset
.