Installer's Information; Installation Checklist; Locating Your Gas Fireplace; Heatwave Duct System Optional Kit #946-556 - Regency Grandview G800C-1 Manual

Table of Contents

Advertisement

Installation Checklist

1. Locate appliance
a)
Room location (Refer to "Locating Your
Gas fireplace" section)
b)
Clearances to Combustibles (Refer to
"Clearances" section)
c)
Mantle Clearances (Refer to "Combustible
Mantel Clearances" section)
d)
Framing & Finishing Requirements (Refer
to "Framing & Finishing" section)
e)
Venting Requirements (Refer to "Venting"
section)
2. Assemble Top Standoffs and Top Facing Support
and Side Nailing Strips (Refer to "Unit Assembly
Prior to Installation" Section). NOTE: Must be
done before installing unit into place.
IMPORTANT: If installing the fan kit or changing
this from rear vent to top vent, this must be
completed prior to installing the appliance
into the framed opening.
3. Install vent (Refer to "Venting" sections).
4. Make gas connections. Test the pilot. Must be
f i r e - p a r t s . c o m
as per Diagram (Refer to "Pilot Adjustment "
section).
Convert to propane if desired (Refer to "Gas
Line Installation" and "Conversion Kit from NG
to LPG" sections).
5. Make electrical connections to receptacle sup-
plied with unit (recommended).
6.
Install standard and optional features. Refer
to the following sections:
a. Standard Glass Door
b. Rear to top vent conversion
c. Coolwall conversion
d. Fan Installation (Optional)
e. Nailing flange installation
f. Electrical access/120 volt power installation
by others
g. Wall Mount On/OFf Switch + Receiver Instal-
lation
h. Coolwall Clearances/Framing/Finishing
i. Clean Front Clearance/ Framing/Finishing
j. Outside Finish Clearance/ Framing/
Finishing
k. LP Conversion (optional)
l. Inner Panels or Brick Panels (Must install one
of the options)
m. Media (Glass crystals)
n. Log Set Installation
o. HeatWave Kit
7. Final check.
This includes:
1. Clocking the appliance to ensure the correct
firing rate (rate noted on label 27,000 Btu/h for
natural gas and propane), after burning appli-
ance for 15 minutes.
2. If required, adjusting the primary air to ensure
that the flame does not carbon. First allow the
unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes
sooting or carboning that results in damage is
not the responsibility of the manufacturer.

Locating Your Gas Fireplace

1. When selecting a location for your fireplace,
ensure that the clearances are met.
2. The appliance must be installed on a flat, solid,
continuous surface For example a wood, metal
or concrete floor or in a raised (on the wall) ap-
plication. The appliance must be installed on a
metal or wood panel extending the full width
and depth of the appliance.
3. The G800C-1 Gas Fireplace can be installed in
a recessed position or framed out into the room
as in A, B, C and D. See Diagram 1.
Diagram 1
A)
Flat on Wall
B)
Flat on Wall Corner
C)
Recessed into Wall/Alcove
D)
Corner

installer's information

4. This appliance is Listed for bedroom installations
using the standard Remote (millivolt thermostat
system). Some areas may have further require-
ments, check local codes before installation.
5. The G800C-1 Gas Fireplace are approved for
alcove installations, see "Clearances" section
for details.
6. We recommend that you plan your installation on
paper using exact measurements for clearances
and floor protection before actually installing this
appliance. Have an authorized inspector, dealer,
or installer review your plans before installation.
HeatWave Duct System
Optional Kit #946-556
The HeatWave Air Duct Kit increases the
effectiveness of your fireplace by dispersing warm
air from the fireplace to remote locations in the
same room or other rooms in your home.
Up to two kits may be installed on the fireplace.
Please Note: Only 1 HeatWave kit may be oper-
ated at one time. This includes the internal blower
option as well.
The HeatWave Duct Kit has different
clearance and framing requirements, check
the HeatWave manual for details.
Using the optional HeatWave kit does not
reduce the size of the ventilation opening,
which must be a minimum of 66 sq. in.
regardless.
Grandview
G800C-1 Gas Fireplace |
®
17