Each of the output groups defined as voice can be mapped to a particular switch and LED on the EVS-VCM/ EVS-RVM and EVS-
SW24. This allows the user to see the state of the voice groups assigned to the switches. This also lets the user individually select which
areas they want to do a live page into. Output groups not defined as voice groups can also be assigned to these switches as long as there
is a voice group already assigned to the group. This allows for dynamically activating/deactivating both voice and strobes/other outputs
in an area with a single button press.
Silencing Options
The following silencing options are available for each output group.
Optional Timers
Silence Inhibit
Auto Silence
Auto Unsilence
Startup Delay
9.4.2 View Group Points
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 2 to view group points.
5.
Enter the group number, then press ENTER.
9.4.3 Edit OPG Template
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 3 to edit OPG Template.
5.
Enter the Template number, then press ENTER
6.
Press ENTER on the template name to edit the name.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Corresponding
Key and LED Numbers
EVS User Interface
Figure 9.4 Corresponding Key and LED for Mapping Output Groups
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
If this option is selected, the output group can be silenced for a programmed time-frame. If the condition that
caused the output to activate has not cleared during the time-frame, the output reactivates. If you select this
option, select the time-frame in the delay field. Range is 0-60 minutes.
When a alarm is generated, the Output group will not activate until the timer expires assuming the event is
still active. Range is 0-120 Seconds
Table 9.2 Silencing Options
Corresponding
Key and LED Numbers
EVS-SW24
Description
119