12.2 SIA / Panels PI Modifier Reporting:

Events are sent to the central station as a variable length string:
The event format is:
EEZZZZ
Where:
EE
Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1.
The account number is sent using an account block that is separate from the event block
2.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
3.
Event parameter can be either a zone, point or module number.
4.
When reporting by point is enabled, the communicator uses a "pi" event to supersedes the actual point event to report the module
the point is linked to.
5.
Panel ID is not sent in the SIA event parameters.
For Example see Table 12.3:
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander
18
SLC Loop Shorted
Program Begin Panel
ID=32
Program Begin Panel ID=
22
AC Power Loss - Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-Nac
Fire Trouble-Nac
12.3 SIA – Panel Communicator:
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
172
Event
Zone
n/a
Zone
n/a
Point
n/a
Point
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Point
n/a
Zone
n/a
Point
n/a
Zone
n/a
Table 12.3 : SIA- Panels - PI Modifier Reporting Examples
n/a97
15
n/a
n/a
05
n/a
01
n/a
123
33
n/a
203
11
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
18
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
97
n/a
200
97
01
n/a
98
n/a
Nac
Circuit 7
98
n/a
Nac
Circuit 7
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
EE-ZZ
FA15
EE-Z
FA5
EE-ZZ /EE-
pi01/FA123
ZZZ
EE-ZZ /EE-
pi11/FA203
ZZZ
EE-ZZ
ET11
EE-Z
RP0
EE-ZZ
YT98
EE-ZZ
YT18
EE-ZZ
ET44
EE-Z
LB0
EE-Z
LB0
EE-Z
AT0
EE-ZZ /EE-
pi97/FT200
ZZZ
EE-Z
FT1
EE-ZZ /EE-
pi98/FT7
Z
Z=Pt. #
EE-ZZZ
FT400
ZZZ=OPG#