This section of the manual is intended to give you an overview of the programming process. Please read this section of the manual care-
fully, especially if you are programming the control panel for the first time.
®
The JumpStart
AutoProgramming feature automates many programming tasks and selects default options for the system. You should
run JumpStart at least once when you are installing the system. See Section 8.1 for details. After you run JumpStart, you may need to do
some additional programming depending on your installation. Section 9 of this manual covers manual programmable options in detail.
Programming the panel can be thought of as a three part process. You must program:
System options. These are options that affect general operation of the panel (see Section 9.6 for details).
Options for input points and zones. These are primarily options that control the detection behavior of devices (see Section 9.5 for
details).
Options for output points and groups. This includes selecting characteristics for output groups and mapping output circuits to output
groups (see Section 9.4 for details).
®
8.1 JumpStart
AutoProgramming
The JumpStart AutoProgramming feature allows for faster system setup. When you run JumpStart AutoProgramming, the panel searches
for expanders and SLC devices not currently in the system. The new devices are added in their default configuration. At the end of the
JumpStart you can choose to not accept the new devices and go back to the configuration you had before. JumpStart saves the installer
from having to program options for each device. Depending on the application, the installer may need to make some changes after Jump-
Start completes.
See Section 8.1.3 for complete details about running JumpStart AutoProgramming.
8.1.1 Input Points
The first JumpStart on the panel in default configuration will determine the number and type of input points (detectors or contact monitor
modules) on each SLC loop. JumpStart AutoProgramming assigns the correct detector type (heat, ionization or photoelectric), so the
installer does not need to edit the device type for detectors. Any contact monitor modules on the system will be assigned type "Manual
Pull." The installer will need to manually change the switch type if manual pull is not correct.
®
The first JumpStart
Group 1.
8.1.2 Output Points
The 6820 JumpStart
assigned as follows:
Circuits 1-6:
Configured as Notification and assigned to Group 1. JumpStart AutoProgramming automatically programs Zone 1 to activate Group 1
using constant on output when an alarm condition occurs.
Circuit 7 (Relay 1):
Assigned to Group 998. JumpStart automatically programs Zone 1 to activate Group 998 using constant on output when a supervisory
condition occurs.
Circuit 8 (Relay 2):
Assigned to Group 999. JumpStart automatically programs Zone 1 to activate Group 999 using constant on output when an alarm occurs.
Amplifier Circuits:
Assigned to Group 2.JumpStart automatically programs Zone 1 to activate Group 2.
Addressable output points (Relay modules):
All addressable relay devices will be configured as "Output Pt" (general purpose output point) and assigned to Group 1.
NOTE: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
8.1.3 Running JumpStart AutoProgramming
Run JumpStart AutoProgramming immediately after you have addressed and connected all input devices (detectors, pull stations, and so
on) and output devices (notification appliances, relays, and so on).
NOTE: If you need to install a few devices after you have run JumpStart, you can install them manually or run JumpStart again at a later time.
JumpStart will keep user options, such as names, for devices already installed. Follow instructions in Section 9 for configuration
To run JumpStart, follow these steps:
1.
Select 7 for Program Menu. Enter the Access Code
2.
Select 6 for JumpStart AutoProgramming.
3.
The message "The system will be shut down during JumpStart." Press ENTER to accept.
4.
When the message, "SLC FAMILY" message appears, select SK or SD; depending on the type of SLC devices the panel is using,
and press ENTER to accept.
5.
A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several
minutes, depending on the number of devices attached.
6.
When the message "Configuring System Done" displays, press any key to continue.
96
Section 8: Programming Overview
AutoProgramming creates one zone (Zone 1) and assigns all input points to Zone 1. Zone 1 is mapped to Output
®
creates three output groups. The 6820/EVS with amplifiers will create four output groups. The output circuits are
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017