4: Point Programming For 5880, 5865, Evs-50W, Evs-Int50W, Evs-100W, Evs-125W And Evs-Ce4 Modules - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

10. Repeat steps 1 through 9 for all circuits.
Choices
Enter Point
Select Type
9.5.4 Point Programming For 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W and
EVS-CE4 Modules
To program 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W, or EVS-CE4 module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 4 to enter point menu.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Function Selections
Type Selections
for each Type
UNUSED
B NOTIF
NOTIF Output
Control Circuit
A NOTIF
AUX_PWR
CONSTANT
AUX RESET
AUX DOOR
Aux SYNC
B SWITCH
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
EVS TAMPER
EVS SUPERVISORY
A SWITCH
Same as B SWITCH
B DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
A DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
Table 9.5 : Menu choices for Internal/External Power Module
Comments
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Aux Power for System Sensor
Refer to comments column of
Table 9.3 for description of these options.
Latch or Non-latching feature only appears for
WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, EVS INPUT, EVS TAMPER,
and EVS SUPERVISORY.
User also has EVS Event Number 1-8 option for
EVS INPUT. Only available when an EVS-VCM is
installed in the system.
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire
CO Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-wire
CO Supervisory detectors
125