2: Point Programming For 6815 Module - Honeywell Silent Knight SK318PT Installation And Operation Manual

Addressable fire system, emergency voice system
Table of Contents

Advertisement

9.5.2 Point Programming For 6815 Module
To program for points on an 6815 module, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for available choices.
Then press ENTER.
5.
Select S for sensor or M for module. (SK Only)
6.
Enter the number of the point you wish to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9.4 under the column heading "Type Selection" for a
list of choices.
Type Selection
UNUSED
DETECTOR
SUP DET
CO SMOKE
DETECTOR
W-DETECTOR
W-SUP-DET
122
Function
Latching Option
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
PHOTO
Latching
Non Latching
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
Latching
FIRE SUPR
Non Latching
Photo
Photo-Heat
Heat
Same as W-
Latching
Detector
Non Latching
Table 9.4 Point Programming for 6815
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Acclimate photoelectric detector.
High temperature heat detector.
Photoelectric detector with heat sensor.
Beam smoke detector.
Use this option when you want a detector to indicate a supervisory
alarm.
Detectors programmed as Supervisory can be latching or non-
latching.
Wireless photoelectric detector
Wireless heat detector