3.
Any Disabling or Activating of points, output groups, or templates from the site at this point will be programmed into the macro.
Do this by going to any annunciator within the site and entering Main Menu -> Point Functions and use Disable/Enable Point or use
I/O Point Control to: disable output groups or individual points, or activate individual points.
4.
Once you are finished with disabling or activating points/output groups, enter the F-Key Recording Menu again and select the 'End
F-KEY Recording' option.
5.
The panel will return to the idle screen.
10.9.2 Aborting an F-Key Macro Recording Session
1.
After an F-Key macro recording session has been started, the session can be canceled at any time by accessing the F-Key Recording
menu and selecting 'Abort F-KEY Recording' option.
2.
The panel will return to the idle screen.
10.9.3 Erasing an F-Key Macro
1.
If an F-Key macro has already been recorded, you can erase it by accessing the F-Key Recording menu and selecting the 'Erase F-
KEY Macro' option.
2.
The panel will return to the idle screen.
10.9.4 Using a Recorded F-Key Macro
1.
From the idle screen on any annunciator in the site, press the F-Key you want to activate.
2.
Once finished, to de-activate the macro press the F-Key again.
10.9.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active event. This is a status type event that can activate outputs without
showing any status on annunciator displays. This should be used for ancillary purposes only.
10.9.6 F-Key Map Inhibit
The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map doesn't exist. This can be
setup to allow for testing purposes where notification of an entire building is not desired during the test. This option is programmable for
each output group map through HFSS Honeywell Fire Software Suite.
When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a trouble event indicating it as
such.
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017