Configuration of manual call points (MCP)

Manual call points should ...
be installed at intervals of max. 100 m in escape and safety routes in workplaces and facilities at risk of fire
be installed so that they are clearly visible and easily accessible
be installed at 1.4 m ± 0.2 m height (pushbutton/control panel above the floor)
receive adequate daylight or illumination from an alternative light source. If security lighting is available, this
should also illuminate the manual call point
if necessary be labelled with an additional transparent adhesive sticker acc. DIN 4066
be clearly labelled if they are not functioning ("not in operation").
In particularly dangerous areas or depending on the use and condition of a building, the distances
between two manual call points should not exceed 40 m. The MCP number and installation position
arrangement must ensure that a person has to cover a distance of no more than 30 m to reach the
next manual call point.
1,4 m
±
0,2 m
Fig. 30: Configuration of manual call points (MCP)
TI 798960.GB0 / 04.20
max. 100 m / 40 m*