6.7
Configuration of manual call points (MCP)
Manual call points should ...
•
be installed at intervals of max. 100 m in escape and safety routes in workplaces and facilities at risk of fire
be installed so that they are clearly visible and easily accessible
•
be installed at 1.4 m ± 0.2 m height (pushbutton/control panel above the floor)
•
receive adequate daylight or illumination from an alternative light source. If security lighting is available, this
•
should also illuminate the manual call point
if necessary be labelled with an additional transparent adhesive sticker acc. DIN 4066
•
be clearly labelled if they are not functioning ("not in operation").
•
In particularly dangerous areas or depending on the use and condition of a building, the distances
between two manual call points should not exceed 40 m. The MCP number and installation position
arrangement must ensure that a person has to cover a distance of no more than 30 m to reach the
next manual call point.
1,4 m
±
0,2 m
Fig. 30: Configuration of manual call points (MCP)
TI 798960.GB0 / 04.20
max. 100 m / 40 m*