Type Selection
SWITCH
(cont.)
NOTIF
RELAY
SLC LED
6820 / 6820EVS Manual P/N LS10144-001SK-E:C 09/28/2017
Function
Latching Option
P.A.S. ACK
Latching
ZONE AUX1
Non Latching
Latching
ZONE AUX2
Non Latching
Latching
SYSTEM AUX1
Non Latching
Latching
SYSTEM AUX2
Non Latching
DETECTOR
Latching
FIRE TAMPER
Non Latching
MANUAL
RELEASE
INTERLOCK
STATUS POINT
Latching
EVS INPUT
Non Latching
Latching
EVS TAMPER
Non Latching
Latching
EVS SUPER-
VISORY
Non Latching
CO DETECT SW
CO
SUPERVISORY
DETECT SW
OUTPUT PT
Select Group
AUX CONST
AUX RESET
AUX DOOR
OUTPUT PT
Select Group
AUX RESET
AUX DOOR
LED NUMBER
01-80
Unused
LED FUNCTION
NOTIF
Table 9.3 Programming Options for 5815XL Modules
Comments
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see , "Edit Zone
Properties").
If an acknowledge switch closes when an alarm or trouble condition
is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type.
The switch must be rated at 5V, 100 mA (minimum) and be used
with an EOL resistor for supervision.
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Performs identically to a supervisory switch, but will be indicated as
a tamper switch on the LCD annunciator.
Manual release switch
Interlock release switch input.
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
CO Detector Switch
CO Supervisory Detector Switch
Output point, a general use notification type. Use for driving
standard notification appliances.
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
Output point, a general use relay type. Use for applications requiring
a relay, such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section 4.16.3
for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if
you were using an auxiliary power supply for door holders, you
would use this option. See Section 4.16.3 for a description of how
this option operates.
For use with SD devices only. 80 sub addresses on LED.
Notification can have group number.