Compatible Alarm Panels - Honeywell HW-TG7LAF02 Installation And Operating Manual

Clss-enabled lte commercial fire alarm communicators
Table of Contents

Advertisement

1 AC
AC power
2 AC
input.

Compatible Alarm Panels

Any UL/ULC/cUL Listed alarm panel that supports one of the following formats is compatible and may be
used with the TG-7 series:
Pulse Formats:
3+1 pulse; 10pps, Double Round, 1400 Hz ack
o
3+1 pulse; 20pps, Double Round, 2300 Hz ack
o
3+1 pulse; 40pps, Double Round, 2300 Hz ack
o
4+2 pulse; 20pps, Double Round, 1400 Hz ack
o
4+2 pulse; 20pps, Double Round, 2300 Hz ack
o
4+2 pulse; 40pps, Double Round, 2300 Hz ack
o
Contact ID
Modem IIe/IIIa
SIA2 (SIA-DC-03 level 2 release at 300 baud)
Sonitrol
DMP
The installer should verify compatibility at the time of installation.
LS10265-000HW-E:C 04/27/2021
Provides primary
Provided AC
operational power to
transformer
the Telguard and
output
battery charging
(12VAC, 10VA).
circuit.
2
/4
firealarmresources.com
AC Power LED ON when AC is normal.
AC power LED OFF and STC LED 2
Flashes 1 time when AC is low.
24