H I P E R G U A R D M V U P S U S E R M A N U A L
W5.146
Sout racked out
W5.149
Sout relay warning
W5.150
Sout relay fault
Sabp unexpectedly ready to transi-
W5.155
tion
W5.156
Sapb racked out
W5.158
Sabp relay warning
W5.159
Sabp relay fault
W5.162
Sabp open request & FB mismatch
W5.164
Output current high
W5.165
Output current too high
W5.170
Output voltage low
W5.177
DRP Ctrl comms link invalid
W5.179
DRP Ctrl SOC at min or max limit
Energy Storage enclosure external IO
W5.180
inputs invalid
MVM enclosure external IO inputs in-
W5.182
valid
W5.184
Internally fed 24V PSU failed
Modbus inputs in APS enclosure IO
W5.185
invalid
24V buffered power supplies not
W5.187
charged warning
MCB open or tripped in APS enclo-
W5.189
sure
Modbus inputs in MVM encl. IO in-
W5.190
valid
W5.192
APS enclosure temperature high
W5.197
DC insulation resistance low
Demand Response Power Controller
W5.211
communications link invalid
Demand Response Power Controller
W5.213
limiting charging
Energy Storage communications link
W5.215
not valid
Table 7.03: List of Warnings and description.
Output Switch circuit breaker is detected as being racked out
from its cubicle.
Output switch circuit breaker relay warning.
Output switch circuit breaker relay fault is detected.
Automatic Bypass switch circuit breaker reports as ready to
transition before software thinks it should.
Automatic Bypass switch circuit breaker is detected as being
racked out from its cubicle.
Automatic Bypass switch circuit breaker relay warning.
Automatic Bypass switch circuit breaker relay fault is de-
tected.
In the Automatic Bypass switch, there has been a mismatch
detected between "open" request and "open" Feedback.
The output current loading on the system exceeds system
nominal rated current by more than a certain percentage.
The system output current has been detected as exceeding
the maximum allowable.
The RMS value of output line voltage has fallen below the low
voltage threshold value.
Demand Response Power Controller communications link not
valid.
Demand Response Power Controller has determined state of
charge of energy storage is at minimum or maximum limit.
Energy Storage enclosure MODBUS INPUTS & OUTPUTS NOT
VALID.
MVM enclosure MODBUS INPUTS & OUTPUTS NOT VALID.
Possible power supply issue or malfunction in APS enclosure.
Possible power supply issue, Ethernet cable fault, Modbus
software malfunction in APS enclosure.
Feedback signal from one of buffer PSU (APS or PE120 enclo-
sure) indicates POWER SUPPLY FAILURE TO CHARGE within a
specified charging period.
One or more MCBs in APS enclosure are OPENED or TRIPPED.
Possible power supply issue, Ethernet cable fault, Modbus
software malfunction in MVM enclosure.
The APS enclosure temperature is measured as HIGHER THAN
A PRESET LEVEL. This indicates COMPROMISED COOLING.
The resistance of DC conductors is LOWER than the defined
limit.
There is a communication problem between the Demand Re-
sponse Power Controller and the MV UPS.
The Demand Response Controller is LIMITING STATE OF
CHARGE of the Energy Storage.
There is a communication problem between the Energy Stor-
age and the MV UPS.